Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T11FR00681

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
04/25/2011 VIOL - FIRE PROTECTION SYSTEMS Approved ALL REPAIRS DONE BY UNITED FIRE
03/23/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. Room 704 kitchen upright installed instead of horizontal sidewall - Shall correct coverage with proper sprinkler head.
2. Garbage room upright installed instead of pendant. - Shall correct coverage with proper sprinkler head.
3. Water flow failed on 8th floor. - Shall repair or replace flow switch.