Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR00681
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ALL REPAIRS DONE BY UNITED FIRE | |
| 03/23/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Room 704 kitchen upright installed instead of horizontal sidewall - Shall correct coverage with proper sprinkler head. 2. Garbage room upright installed instead of pendant. - Shall correct coverage with proper sprinkler head. 3. Water flow failed on 8th floor. - Shall repair or replace flow switch. |