Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
05/11/2011 VIOL - FIRE PROTECTION SYSTEMS Approved
03/21/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. All sprinkler heads need to be replaced. They are dated 1960 & 1961. - According to the report all sprinkler heads that are 50 years old or more should be replaced - under NFPA 25 Section 5.3.1.1.1 shall be replaced or representative samples from one or more areas shall to tested. Test procedures shall be repeated at 10 year internals.
2. Both inspectors test valve and water motor gong tests failed - Shall repair or replace both valve and water motor gong.
3. No lock on control valve. - Shall properly lock control valve