Case: T11FR00666

Parcel: 12416008A


Addresses:

601 E 24TH ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
04/26/2011 VIOL - FIRE PROTECTION SYSTEMS Approved Gramthan Fire Protection did the work.
03/21/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. There is a total of 32 heads that are more than 50 years old and should be replaced - under NFPA 25 (11-2008ED) Section 5.3.1.1.1 shall be replaced or representative samples from one or more areas shall to tested. Test procedures shall be repeated at 10 year internals.
2. Pipe at North West of warehouse is bent and needs to be replaced.