Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T11FR00660

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
10/30/2013 VIOL - FIRE PROTECTION SYSTEMS Approved Sprinkler system corrected and fire pump installed final testing and corrections completed on 05.05.2013.
03/28/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required Called and set up a meeting with Mr. R. Myers for this Tuesday 3/29/2011 at 2:00pm.
03/21/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. There is no sprinkler coverage under structure in production area - shall correct sprinkler cover, will need an approved plan and permit.
2. Northwest sprinkler head in tool room needs to be lowered
3. Missing escutcheons in tool room (x3) storage room
4. Missing escutcheon in men's bathroom (x1) next to break room
5. There is no coverage at north west corner of production area shall correct sprinkler coverage, will need an approved plan and permit.
03/21/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required Received e-mail with an attachment from Mr. Rich Myers at 724-972-2792 the attachment was a copy of a service report from United fire protection stating they installed one new head and replace escutcheons, nothing was done on #1 and #5 of the report.