Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR00660
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2013 | VIOL - FIRE PROTECTION SYSTEMS | Approved | Sprinkler system corrected and fire pump installed final testing and corrections completed on 05.05.2013. | |
03/28/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Called and set up a meeting with Mr. R. Myers for this Tuesday 3/29/2011 at 2:00pm. | |
03/21/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. There is no sprinkler coverage under structure in production area - shall correct sprinkler cover, will need an approved plan and permit. 2. Northwest sprinkler head in tool room needs to be lowered 3. Missing escutcheons in tool room (x3) storage room 4. Missing escutcheon in men's bathroom (x1) next to break room 5. There is no coverage at north west corner of production area shall correct sprinkler coverage, will need an approved plan and permit. |
|
03/21/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Received e-mail with an attachment from Mr. Rich Myers at 724-972-2792 the attachment was a copy of a service report from United fire protection stating they installed one new head and replace escutcheons, nothing was done on #1 and #5 of the report. |