Case: T11FR00655

Parcel: 120060660


Addresses:

3901 S 6TH AV

Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
03/17/2011 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
03/17/2011 VIOL - MEANS OF EGRESS Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate…
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator.

_____ Repair or replace emergency lighting