Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR00642
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/11/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
03/16/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Clear area from the inspectors test valve. (ITV) 2. Repair or replace main control valve unable to shut down. 3. Repair or replace water motor gong & electric bell failed to work when tested. Re-inspection is set for April 13, 2011. |