Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - REINSPECTION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2011 | INSP - REINSPECTION | Correction Required | Upon following up I found that the cooking appliance was indeed to large for the actual hood system as mentioned in the "Deficiencie" report. The gap distance was to large to properly filter cooking vapors and to reduce heat from cooking. I followed up with a full fire inspection refer to T11FR00646 for further information. ________________________________ (Inspector Longo) ____________________________ (Captain) |