Case: T11FR00483

Parcel: 13403044A


Addresses:

9101 E 22ND ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T11FR00483

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
03/24/2011 INSP - FULL Approved
02/23/2011 INSP - FULL Correction Required 1. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
- DESK IN THE REAR OF THE SHOP AREA
- GOING FROM REAR OFFICE THROUGHT H ERAFTER TO THE TV

2. _____ 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
- DESK IN THE REAR OF THE BUSINESS

3. _____ 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exits:
- REMOVE THE LOCKING HASP ON THE REAR EXIT DOOR

4. _____ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used: ABATE ELECTRICAL HAZARDS
- WIRES GOING FROM LIGHT TO ANOTHER FIXTURE IN THE PHOTO ROOM
- REPLACE THE MISSING LIGHT SWITCH COVER IN THE PHOTO ROOM
- REPLACE THE COVER ON THE J-BOX ON THE REAR WALL IN THE STORAGE AREA

5. _____ 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
-REPLACE MISSING ELECTRICAL COVERPLATE IN THE WAITHING ROOM

6. _____ 2703.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing compressed gases shall be conspicuously labeled:
- 2 IN THE REPAIR SHOP
- ONE OUTSIDE BY THE TANKS

7. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
- SERVIE THE FRIE EXTINGUSHER IN THE REPAIR SHOP NEAR REAR EXIT DOOR

8. _____ 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official.
- REAR EXIT IS BLOCKED INSIDE AND OUTSIDE WITH STOCK

9. _____ 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or Shielding so that ignition cannot occur. Provide good housekeeping:
-CU7RRENTLY THERRE ARE SHAVIGNS THROUGH THE REAR AREA FO THE REPAIR SHOP
-CLEAN UP THE OIL INSIDE THE REPAIR SHOP THAT IS ON THE GROUND
- MAINTAIN CLEAR AND IDENTIFYABLE AISLES