Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR00473
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 01/03/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Sprinkler to close to lights in hall by: #381-390-660-649-640-148-31-38-211-182-172-329-321-305 (Correct coverage) 2. The following units have had walls removed and sprinklers are too close together: #819-944-707-767-770-672-586-592-391-40 (Correct coverage) 3. In the apartment heads missing escutcheons. (Replace missing escutcheons) 4. Pressure gauges are outdated. (repair or replace gauges) 5. Sectional control valve is not locked or electronically supervised. (All valves on all floors shall be chain and locked or electronically supervised) 6. Water motor gong does not work. (Repair or replace bell) 7. 5 year check valve inspection pass due. (Need a 5 year inspection done, last inspection done 09/19/1986.) |