Case: T11FR00473

Parcel: 13505149Y


Addresses:

2501 S WILMOT RD


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T11FR00473

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
03/30/2011 VIOL - FIRE PROTECTION SYSTEMS Approved
01/03/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. Sprinkler to close to lights in hall by:
#381-390-660-649-640-148-31-38-211-182-172-329-321-305 (Correct coverage)
2. The following units have had walls removed and sprinklers are too close together:
#819-944-707-767-770-672-586-592-391-40 (Correct coverage)
3. In the apartment heads missing escutcheons. (Replace missing escutcheons)
4. Pressure gauges are outdated. (repair or replace gauges)
5. Sectional control valve is not locked or electronically supervised. (All valves on all floors shall be chain and locked or electronically supervised)
6. Water motor gong does not work. (Repair or replace bell)
7. 5 year check valve inspection pass due. (Need a 5 year inspection done, last inspection done 09/19/1986.)