Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T11FR00472
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/04/2011 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. | |
02/18/2011 | INSP - FULL | Violation | 1.) TFC 605.5 THE EXTENTION CORD BEING USED IN MOM/BABY WAITING ROOM IS NOT PERMITTED BY THE FIRE CODE. | |
02/18/2011 | INSP - FULL | Violation | 2.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN STORAGE AREA ALCOVE NEXT TO CLEAN LINEN ROOM IN SOUTH HALLWAY OF MOM/BABY. | |
02/18/2011 | INSP - FULL | Violation | 3.) TFC 3004.1 O2 BOTTLES IN PICU EQUIPMENT ROOM NEXT TO MANAGER'S ROOM MUST BE STORED IN UPRIGHT POSITION. | |
02/18/2011 | INSP - FULL | Violation | 4.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN G.I. INTAKE ROOM. | |
02/18/2011 | INSP - FULL | Violation | 5.) TFC 1028.2 REMOVE ITEMS IN CORRIDOR NOT ON WHEELS IN G.I. BREAKROOM CORRIDOR. | |
02/18/2011 | INSP - FULL | Violation | 6.) TFC 901.6 IN G.I. WASH ROOM REPLACE (1) SPRINKLER HEAD ESCUTHCEON WITH PROPER SIZE ESCUTCHEON. |