Case: T11FR00462

Parcel: 124150240


Addresses:

817 E 18TH ST


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T11FR00462

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2011 VIOL - FIRE PROTECTION SYSTEMS Approved Allan Fire Protection did all repairs on March 11, 2011.
02/17/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. Riser has several areas of external corrosion - Repair or replace as needed.
2. First floor center office - There is a star 165 degree chrome pendent with cap that is coated with texture compound. - Shall repair or replace
3. No record of a current 5 year internal check valve inspection done - Shall have a 5 year internal check valve inspection done.