Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | Allan Fire Protection did all repairs on March 11, 2011. | |
| 02/17/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Riser has several areas of external corrosion - Repair or replace as needed. 2. First floor center office - There is a star 165 degree chrome pendent with cap that is coated with texture compound. - Shall repair or replace 3. No record of a current 5 year internal check valve inspection done - Shall have a 5 year internal check valve inspection done. |