Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2013 | VIOL - FIRE PROTECTION SYSTEMS | Approved | SPRINKLER INSTALLED Appeal to the chief on not requiring the parking structure to be sprinklered, appeal approved use only for parking and no storage allowed. |
|
| 04/04/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Need to correct sprinkler coverage under outside canopies attached to build on east side. Note: will need an approved plan and permit before work is done. | |
| 02/16/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Unable to test main drain due to hole in piping - Shall repair or replace piping so that a 2" drain test can be done. 2. System is due for 5 year internal valve inspection - Shall complete a 5 year inspection and also record 2" flow test. |