Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/16/2011 |
INSP - FULL |
|
Approved |
ALL OTED TFC VIOLATIONS HAVE BEEN CORRECTED. |
| 02/16/2011 |
INSP - FULL |
|
Violation |
1.) TFC 315.2.1 MAINTAIN STORAGE 18" BELOW SPRINKLER HEAD DEFLECTOR IN CLOSET OF MOLLY'S OFFICE. |
| 02/16/2011 |
INSP - FULL |
|
Violation |
2.) TFC 315.2.3 STORAGE IS BLOCKING ACCESS TO ELECTRICAL BREAKER PANEL IN JANITOR'S OFFICE. |
| 02/16/2011 |
INSP - FULL |
|
Violation |
3.) TFC 901.6 SPRINKLER HEAD MUST BE LOWERED AND AN ESCUTCHEON IN PLACE IN SERVER ROOM. |
| 02/16/2011 |
INSP - FULL |
|
Violation |
4.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT IN HALLWAY SOUTH OF CONNECTING PATIO IS NOT LIGHTING. |
| 02/16/2011 |
INSP - FULL |
|
Violation |
5.) TFC 1006.3 CHECK ALL EMERGENCY ILLUMINATION UNITS FOR PROPER OPERATION IN ADELANTE BUILDING. |
| 02/16/2011 |
INSP - FULL |
|
Violation |
6.) TFC 605.6 PUT THE COVER PLATE IN PLACE ON ELECTRICAL JUNCTION BOX IN RISER ROOM. |
| 02/16/2011 |
INSP - FULL |
|
Violation |
7.) TFC 605.4.2 POWER STRIPS IN MARCO'S CUBICLE CASNNOT BE PIGGY BACKED TOGETHER. |
| 02/16/2011 |
INSP - FULL |
|
Violation |
8.) TFC 901.6 A DROP CEILING MUST BE IN PLACE IN WATER HEATER CLOSET. |