Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 02/10/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Shall correct sprinkler coverage in the file/records room. Sprinkler head is 8' 2" from one wall, can not be more than 7' 6" from any wall. This room is not a light hazard but a ordinary hazard class. 2. Office are being used as a storage room 1 sprinkler head is 8' 2" off one wall, can not be more than 7' 6" off any wall. Again storage is ordinary hazard and office is light hazard. |