Case: T11FR00420

Parcel: 12108309A


Addresses:

6226 E PIMA ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
04/11/2011 VIOL - FIRE PROTECTION SYSTEMS Approved
02/10/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. Shall correct sprinkler coverage in the file/records room. Sprinkler head is 8' 2" from one wall, can not be more than 7' 6" from any wall. This room is not a light hazard but a ordinary hazard class.
2. Office are being used as a storage room 1 sprinkler head is 8' 2" off one wall, can not be more than 7' 6" off any wall. Again storage is ordinary hazard and office is light hazard.