Case: T11FR00356

Parcel: 13416205D


Addresses:

7107 E 22ND ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T11FR00356

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
03/03/2011 INSP - FULL Approved
02/07/2011 INSP - FULL Correction Required 1. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
- J-BOX TO EXTEBNSION CORD IN THE SHOP AREA
- GOIGN THROUGH THE RAFTERS IN THE STOCK AREA
- GOING UNDER THE DOOR TO THE DISPLAY AREA

2. _____ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used:.
- REMOVE SPLICED CORD GONIG TO THE LIGHTS IN THE COMPRESSOR ROOM
- PLACE A "BLANK" IN THE ELCTRICAL PANEL WHERE THE BREAKER IS MISSING

3. _____ 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3.
- IN THE COMPRESSOR ROOM

4. _____ 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.
- REAR EXIT FROM DISPLAY FLOOR (ALSO PANIC HARDWARE SHALL BE THE ONLY LOCKING DEVICE ON THE DOOR-IFC 1028.6.)

5. _____ 1028.2/ 1008.1.8 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official.
- CURRENTLY THE REAR EXIT FROM THE STOCK ROOM HAS A BAR ACROSS IT, A DOUBLE-KEY LOCKING DEVICE, AND SLIDE BOLTS.

REQUIRED ACTION:
- REMOVE THE BARD AND ASSOCIATED HARDWARE
- PROVIDE A THUMB-LATCH DEVICE IF YOU ARE GONIG TO USE A DEADBOLT TO SECURE THE DOOR
- REMOVE THE SLIDEBOLTS ON THE DOOR