Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T11FR00340

Parcel: 10512020C


Addresses:

4136 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T11FR00340

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/04/2011 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.3 Locks and latches.
Locks and latches shall be permitted to prevent operation of doors where any of the following exists…
-- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress
side provided:
-- 2.1. The locking device is readily distinguishable as locked,
-- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background,
-- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause.

_____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main
egress door.

1027.5 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027.

_____ Fix, repair, or replace the emergency lighting unit(s) in order to meet code standards






________________________________________________
(Joseph P. Longo, Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report.
(Building Representative)

____________________________
(Captain)

Re-inspection scheduled on or after ___/___/___
Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions.
Thank you.

Re-inspection passed: ___ ___ ___


___________________ Passed on: ________
(Joseph P. Longo)