Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2011 | VIOL - MEANS OF EGRESS | Approved | ||
| 02/02/2011 | VIOL - MEANS OF EGRESS | Violation | 1027.4 Power source. Where emergency illumination is required in Section 1027.5, exit signs shall be visible under emergency illumination conditions. ____Repair EXIT sign in pool room. ____Repair EXIT sign in west hall. |
|
| 02/02/2011 | VIOL - MEANS OF EGRESS | Violation | 1027.5 Illumination emergency power. ____Repair all the following emergency lighting units: ____Chapter room. ____Front entrance foyer. ____West hall. ____North hall. |
|
| 02/02/2011 | VIOL - MEANS OF EGRESS | Violation | 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. ____The new front exit needs to have an exit sign. Punch out the plastic arrow in the old sign that will direct occupants towards the new exit. |