Case: T11FR00327

Parcel: 12402043A


Addresses:

1605 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
04/28/2011 VIOL - FIRE PROTECTION SYSTEMS Approved
02/02/2011 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

____Provide a copy of sprinkler inspection report. Correct any deficiencies.
____Provide a copy of fire alarm inspection report. Correct any deficiencies.
____Provide a copy of hood inspection report. Correct any deficiencies.
____Complete smoke detector log. Provide upon reinspection.
02/02/2011 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.7 Separation. All deep fat fryers shall be installed with at least a 16 inch space between the fryer and surface flames of adjacent cooking appliances.
EXCEPTION: Where a steel or tempered glass baffle plate is installed at a minimum 8 inches in height between the fryer and surface flames of the adjacent cooking appliance, the requirement for a 16 inch space shall not apply. Where the fryer and the surface flames of the adjacent cooking appliance are at different horizontal planes, the minimum height or 8 inches shal be measured from the higher of the two.

____Install a permanent baffle plate.
02/02/2011 VIOL - FIRE PROTECTION SYSTEMS Violation 906.9 Height above floor. Portable fire extinguishers having a
gross weight not exceeding 40 pounds (18 kg) shall be installed
so that its top is not more than 5 feet (1524 mm) above the floor.
Hand-held portable fire extinguishers having a gross weight
exceeding 40 pounds (18 kg) shall be installed so that its top is
not more than 3.5 feet (1067 mm) above the floor. The clearance
between the floor and the bottom of installed hand-held
extinguishers shall not be less than 4 inches (102 mm).

____Lower the extinguisher in living room. Needs to be mounted so the top is not higher than 5ft above the floor.
02/02/2011 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall
be selected, installed and maintained in accordance with this
section and NFPA 10.

____Replace missing extinguisher in south hall cabinet.