Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 02/02/2011 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Provide a copy of sprinkler inspection report. Correct any deficiencies. ____Provide a copy of fire alarm inspection report. Correct any deficiencies. ____Provide a copy of hood inspection report. Correct any deficiencies. ____Complete smoke detector log. Provide upon reinspection. |
|
| 02/02/2011 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.7 Separation. All deep fat fryers shall be installed with at least a 16 inch space between the fryer and surface flames of adjacent cooking appliances. EXCEPTION: Where a steel or tempered glass baffle plate is installed at a minimum 8 inches in height between the fryer and surface flames of the adjacent cooking appliance, the requirement for a 16 inch space shall not apply. Where the fryer and the surface flames of the adjacent cooking appliance are at different horizontal planes, the minimum height or 8 inches shal be measured from the higher of the two. ____Install a permanent baffle plate. |
|
| 02/02/2011 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). ____Lower the extinguisher in living room. Needs to be mounted so the top is not higher than 5ft above the floor. |
|
| 02/02/2011 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Replace missing extinguisher in south hall cabinet. |