Case: T11FR00305

Parcel: 135084470


Addresses:

7230 E 22ND ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/28/2011 INSP - FULL Approved
01/31/2011 INSP - FULL Correction Required 1. _____ 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3.
-2 EACH

2. _____ 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system
- EMERGENCY LIGHTS IN THE BACK ROOM

3. _____ 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
- SHALL BE CLEANED EVERY 6 MONTHS LAST 2009
- REPLACE MISING FILTERS

3. _____ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated
- REPLACE THE MISSING FIRE RATED DOOR BETWEEN THE KITCHEN AND THE REAR AREA.