Case: T11FR00302

Parcel: 135084480


Addresses:

7234 E 22ND ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/14/2011 INSP - FULL Approved APPROVED
01/31/2011 INSP - FULL Correction Required 1. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
-ONE IS A HALON
-ONE THAT WAS LAST TESTED IN 1997

2. _____ 2703.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing compressed gases shall be conspicuously labeled:
- LABEL 55 GALLON DRUM "ANTIFREEZE"
- LABEL ALL OUTSIDE TANKS "USED OIL"

3. _____ 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exits:
- Places of detention or restraint.
- In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in churches, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided:
2.1. The locking device is readily distinguishable as locked,
2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25mm)high on a contrasting background,
- PROVIDE THUMB-LATCH LOCKING DEVICE
- REMOVE LOCKING HASP

4. _____ 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exits:
" Places of detention or restraint.
" In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in churches, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided:
2.1. The locking device is readily distinguishable as locked,
2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25mm)high on a contrasting background,
-PROVIDE SIGN ON THE MAIN FRONT DOOR