Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2011 | VIOL - BUILDING SVCS & SYSTEMS | Approved | All items abated. | |
| 01/27/2011 | VIOL - BUILDING SVCS & SYSTEMS | Continued | ___Electrical outlet needs cover. (2nd grade room) 2006 IFC 605.6 Open juncton boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all swith and outlet boxes. ***INSTALL COVERS TO ELECTRICAL BOXES. |
|
| 01/27/2011 | VIOL - BUILDING SVCS & SYSTEMS | Continued | ___Unapproved electrical multi-plug adapters. (8th grade room) 2006 IFC 605.4 Multi-plug adapters, such as as cube adapters, usfused plug strips shall be prohibited. ***REPLACE STRIP WITH A UL LISTED, FUSED POWER TAP PLUGGED DIRECTLY TO A PERMANENT RECEPTACLE. |
|
| 01/27/2011 | VIOL - BUILDING SVCS & SYSTEMS | Continued | ___Extension cords used as permanent wiring. (8th grade room) 2006 IFC 605.5 Extension cords shall not be a substitute for permanent wiring. ***REPLACE EXTENSION CORD WITH A UL LISTED, FUSED POWER TAP WITH A LONGER CORD TO REACH COMPUTER. |