Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T11FR00237

Parcel: 137053090


Addresses:

5242 S 12TH AV


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T11FR00237

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
01/26/2011 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.To ensure that there is no confusion on the required exiting from the building the following must be completed: A sign stating "THIS DOOR BLOCKED" affixed to the exterior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background.