Case: T11FR00212

Parcel: 13314236C


Addresses:

7063 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T11FR00212

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Approved

Date Description Inspector Results Comments
04/12/2011 VIOL - PRECAUTION AGAINST FIRE Approved
01/21/2011 VIOL - PRECAUTION AGAINST FIRE Violation Clearance below sprinklers:
TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.

______Remove storage to 18 inches or more below sprinkler head.