Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/17/2011 INSP - FULL Approved approved
01/20/2011 INSP - FULL Correction Required 1. _____ 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exits:
- Places of detention or restraint.
- In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in churches, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided:
-2.1. The locking device is readily distinguishable as locked,
-2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25mm)high on a contrasting background,
-2.3. The use of the key-operated locking device is revokable by the fire code official for due cause.

REQUIRED ACTION: PLACE A SIGN IN BOTH UNITS ON THIS PROPERTY AT THE MAIN FRONT EXITS

2. _____ 407.2 Material Safety Data Sheets. Material Safety Data
Sheets (MSDS) for all hazardous materials shall be readily
available on the premises.

3. _____ 407.4 Training. Persons responsible for the operation of areas in which hazardous materials are stored, dispensed, handled or used shall be familiar with the chemical nature of the materials and the appropriate mitigating actions necessary in the event of
a fire, leak or spill…
- Train employees on the location of the MSDS/ Hazardous Communication Program.

4. _____ 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official.
-PLACE THE PROPER SIGN AT THE ENTRANCE TO THE BUILDING 704M PLACARD 3-HEALTH 0-FLAMMABILTY 1-REACTIVITY

5. _____ 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.
- REAR EXIT