Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
02/28/2011 VIOL - FIRE PROTECTION SYSTEMS Approved PIPING PENETRATION WAS SEALED. MANUAL PULL ACTIVATION DEVICE WAS MOVED. APPROVED.
01/19/2011 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6 REPAIR DEFICIENCIES NOTED ON 6 MO. INSPECTION REPORT DATED 01/04/11:
1.) PIPING THAT PENETRATES THE HOOD MUST BE PROPERLY SEALED TO PREVENT GREASE FROM GETTING BEHIND THE GREASE BAFFLES.
2.) HAVE MANUAL ACTIVATION DEVICE MOVED TO AT LEAST 10' AND NOT MORE THAN 20' FROM THE COOKING EQUIPMENT. HAVE REPAIRS DONE WITHIN 30 DAYS.