Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | PIPING PENETRATION WAS SEALED. MANUAL PULL ACTIVATION DEVICE WAS MOVED. APPROVED. | |
| 01/19/2011 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6 REPAIR DEFICIENCIES NOTED ON 6 MO. INSPECTION REPORT DATED 01/04/11: 1.) PIPING THAT PENETRATES THE HOOD MUST BE PROPERLY SEALED TO PREVENT GREASE FROM GETTING BEHIND THE GREASE BAFFLES. 2.) HAVE MANUAL ACTIVATION DEVICE MOVED TO AT LEAST 10' AND NOT MORE THAN 20' FROM THE COOKING EQUIPMENT. HAVE REPAIRS DONE WITHIN 30 DAYS. |