Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T11FR00178

Parcel: 134113640


Addresses:

8099 E 22ND ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T11FR00178

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/01/2011 INSP - FULL Approved all items abated
01/19/2011 INSP - FULL Correction Required 1. _____ 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose
- FRONT EXIT
- REAR EXIT

2. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances
- ELECTRICAL DEPARTMENT

3. _____ 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.
- REAR EXIT

4. _____ 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system
- REAR COORIDOR