Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 01/19/2011 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Pull station clear and identifiable: TFC2006/ 904.11.4 Special provisions for automatic sprinkler systems. Automatic sprinkler systems protecting commercial- type cooking equipment shall be supplied from a separate, readily accessible, indicating-type control valve that is identified. ______ Clear area around pull station and have it clearly marked. |
|
| 01/19/2011 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Hood needs cleaning: 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. ______ Clean hood in an acceptable manner and maintain it this way. [Please have them "professionally cleaned"] ______ ***** ONLY USE GRILL AND FRYERS AND ALL OTHER COOKING APPLIANCES WHEN ALL THE GREASE COLLECTING SCREENS ARE IN PLACE! ***** [If found using otherwise you will be "red tagged" and pre-cited. This is very important as your business could easily catch fire with the misuse of the safety equipment.] |