Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T11FR00164
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2011 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. | |
| 01/14/2011 | INSP - FULL | Violation | 1.) TFC 605.5 AN EXTENSION CORD CANNOT BE USED AS SUBSTITUTE FOR PERMANENT WIRING ON 5TH FLOOR CENTRAL, CMG TRIAGE NURSES CUBICLES. | |
| 01/14/2011 | INSP - FULL | Violation | 2.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER ON 5TH FLOOR CENTRAL, CMG TRIAGE NURSES CUBICLES. | |
| 01/14/2011 | INSP - FULL | Violation | 3.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER IN AHCCS OFFICE ON 4TH FLOOR NORTH. | |
| 01/14/2011 | INSP - FULL | Violation | 4.) TFC 1028.2 TRASH CANS AND SHARPS CONTAINERS NOT ON WHEELS MUST BE REMOVED FROM CORRIDOR IN COMPLEX WOUND UNIT. | |
| 01/14/2011 | INSP - FULL | Violation | 5.) TFC 901.6 SMALL UPRIGHT CEILING TILE ON 3RD FLOOR WEST IN ROOM #3337 MUST BE KEPT IN PLACE. | |
| 01/14/2011 | INSP - FULL | Violation | 6.) TFC 315.2.1 STORAGE MUST BE MAINTAINED 18" BELOW SPRINKLER HEAD ESCUTCHEON ON 1ST FLOOR NORTH IN ROOM #1016H. | |
| 01/14/2011 | INSP - FULL | Violation | 7.) TFC 901.6 SPRINKLER HEAD ESCUTCHEON IN ENLARGED HOLE IN CEILING TILE IS NOT REMAINING IN PLACE ON 1ST FLOOR CENTRAL IN BAKER'S DELI. | |
| 01/14/2011 | INSP - FULL | Violation | 8.) TFC 605.4.2 POWER STRIPS CANNOT BE PIGGY BACKED TOGETHER IN ROOM # CD 1403 OF RADIOLOGY. | |
| 01/14/2011 | INSP - FULL | Violation | 9.) TFC 605.4.2 POWER STRIPS IN TWO LOCATIONS IN ROOM # 1435 OF MRI CANNOT BE PIGGY BACKED TOGETHER. | |
| 01/14/2011 | INSP - FULL | Violation | 10.) TFC 703.1.1 REPLACE MISSING FIRE SEAL AROUND CONDUIT IN MOB ON 2ND FLOOR SOUTH, ROOM # 2932. | |
| 01/14/2011 | INSP - FULL | Violation | 11.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT #039922 IN HALLWAY OUTSIDE OF SUITE 202 IS NOT WORKING. | |
| 01/14/2011 | INSP - FULL | Violation | 12.) TFC 901.6 REPLACE BROKEN CEILING TILE IN SUITE 200, PIMA HEART, ROOM # 2967. | |
| 01/14/2011 | INSP - FULL | Violation | 13.) TFC 315.2.1 MAINTAIN STORAGE 18" BELOW SPRINKLER HEAD DEFLECTOR IN CLOSET #2913A ON 2ND FLOOR SOUTH. | |
| 01/14/2011 | INSP - FULL | Violation | 14.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER IN TELECOM ROOM IN BASEMENT. | |
| 01/14/2011 | INSP - FULL | Violation | 15.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER IN BIO MED ROOM #0120B IN BASEMENT. | |
| 01/14/2011 | INSP - FULL | Violation | 16.) TFC 605.5 THE EXTENSION CORD BEING USED IN BIO MED ROOM, #1 WORK STATION IN NORHWEST CORNER CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. | |
| 01/14/2011 | INSP - FULL | Violation | 17.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER IN NUTRITION SERVICES CLERK'S OFFICE. IN TWO PLACES. | |
| 01/14/2011 | INSP - FULL | Violation | 18.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER ON EAST WALL IN LINEN ROOM IN BASEMENT. |