Case: T11FR00164

Parcel: 11615088L

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T11FR00164

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2011 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED.
01/14/2011 INSP - FULL Violation 1.) TFC 605.5 AN EXTENSION CORD CANNOT BE USED AS SUBSTITUTE FOR PERMANENT WIRING ON 5TH FLOOR CENTRAL, CMG TRIAGE NURSES CUBICLES.
01/14/2011 INSP - FULL Violation 2.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER ON 5TH FLOOR CENTRAL, CMG TRIAGE NURSES CUBICLES.
01/14/2011 INSP - FULL Violation 3.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER IN AHCCS OFFICE ON 4TH FLOOR NORTH.
01/14/2011 INSP - FULL Violation 4.) TFC 1028.2 TRASH CANS AND SHARPS CONTAINERS NOT ON WHEELS MUST BE REMOVED FROM CORRIDOR IN COMPLEX WOUND UNIT.
01/14/2011 INSP - FULL Violation 5.) TFC 901.6 SMALL UPRIGHT CEILING TILE ON 3RD FLOOR WEST IN ROOM #3337 MUST BE KEPT IN PLACE.
01/14/2011 INSP - FULL Violation 6.) TFC 315.2.1 STORAGE MUST BE MAINTAINED 18" BELOW SPRINKLER HEAD ESCUTCHEON ON 1ST FLOOR NORTH IN ROOM #1016H.
01/14/2011 INSP - FULL Violation 7.) TFC 901.6 SPRINKLER HEAD ESCUTCHEON IN ENLARGED HOLE IN CEILING TILE IS NOT REMAINING IN PLACE ON 1ST FLOOR CENTRAL IN BAKER'S DELI.
01/14/2011 INSP - FULL Violation 8.) TFC 605.4.2 POWER STRIPS CANNOT BE PIGGY BACKED TOGETHER IN ROOM # CD 1403 OF RADIOLOGY.
01/14/2011 INSP - FULL Violation 9.) TFC 605.4.2 POWER STRIPS IN TWO LOCATIONS IN ROOM # 1435 OF MRI CANNOT BE PIGGY BACKED TOGETHER.
01/14/2011 INSP - FULL Violation 10.) TFC 703.1.1 REPLACE MISSING FIRE SEAL AROUND CONDUIT IN MOB ON 2ND FLOOR SOUTH, ROOM # 2932.
01/14/2011 INSP - FULL Violation 11.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT #039922 IN HALLWAY OUTSIDE OF SUITE 202 IS NOT WORKING.
01/14/2011 INSP - FULL Violation 12.) TFC 901.6 REPLACE BROKEN CEILING TILE IN SUITE 200, PIMA HEART, ROOM # 2967.
01/14/2011 INSP - FULL Violation 13.) TFC 315.2.1 MAINTAIN STORAGE 18" BELOW SPRINKLER HEAD DEFLECTOR IN CLOSET #2913A ON 2ND FLOOR SOUTH.
01/14/2011 INSP - FULL Violation 14.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER IN TELECOM ROOM IN BASEMENT.
01/14/2011 INSP - FULL Violation 15.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER IN BIO MED ROOM #0120B IN BASEMENT.
01/14/2011 INSP - FULL Violation 16.) TFC 605.5 THE EXTENSION CORD BEING USED IN BIO MED ROOM, #1 WORK STATION IN NORHWEST CORNER CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING.
01/14/2011 INSP - FULL Violation 17.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER IN NUTRITION SERVICES CLERK'S OFFICE. IN TWO PLACES.
01/14/2011 INSP - FULL Violation 18.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER ON EAST WALL IN LINEN ROOM IN BASEMENT.