Case: T11FR00136

Parcel: 13421095E


Addresses:

108 S KOLB RD


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T11FR00136

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
01/11/2011 INSP - FULL Violation TFC 505.1 - Address numbers.
New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements.

_____ Provide address numbers (108) for entrance to suite that are at least 3" in height and visible from the parking lot.

TFC 605.1 - Abatement of electrical hazards.
Identified electrical hazards shall be abated.

_____ Replace outlet in kitchenette with one that is GFCI protected.

TFC 605.4 - Multiplug adapters.
Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

_____ Remove multiplug adaptor serving AV system.

TFC 605.4.2 - Power supply.
Relocatable power taps shall be directly connected to a permanently installed receptacle.

_____ Plug power strips directly into wall outlet (office).

Chapter 906, Portable Fire Extinguishers
TFC 906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. (Professional maintenance yearly, manual inspection monthly, affix a tag to the extinguisher with records of these activities.)

_____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.