Case: T11FR00079

Parcel: 13613027F


Addresses:

3411 S CAMINO SECO


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T11FR00079

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
01/20/2011 INSP - FULL Approved NOTE: TFD REQUIRED A COMPLAINT HOOD. OTHER ITEMS LISTED ON THE PROPOSDAL SUCH AS CANINETS, SINK ETC DID NOT COME FROM TFD.

FINAL HOOD INSPECTION TO BE COMPLETED DURING THE PERMIT PROCESS.
01/10/2011 INSP - FULL Correction Required 1. Section 1028.6 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.
- ASSEMBLY ROOM 2 EACH

2. _____ 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose.
- 2 EACH IN ASSEMBLY ROOM

3. _____ 904.2.1 Commercial hood and duct systems. Each required commercial kitchen exhaust hood and duct system required by Section 610 to have a Type I hood shall be protected with an approved automatic fire-extinguishing
- A hood system shall be instaleld for your stove. THe hood shall be capable of removing grease-laden vapors . Currently there is no hood and an inadequate fan. You are hereby ordered to cease and desist all cooking operations until you have a compliant hood.

4. _____ 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
- REPLAVE THE MISSING ELECTRICAL COVERPLATE ON THE SHUFFLEBOARD ROOM