Case: T11FR00030

Parcel: 133110200


Addresses:

7189 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T11FR00030

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
02/15/2011 VIOL - BUILDING SVCS & SYSTEMS Approved
01/05/2011 VIOL - BUILDING SVCS & SYSTEMS Violation Blocked electrical panel:

TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.

______Clear area in front of electrical panel in an approved manner.
[magnetic sign must be relocated] OK after reconsideration...