Permit: T11EL03301

Parcel: 12218126A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/16/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/13/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
02/07/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MULTIPLE TERMINATIONS AT GROUND LUG PER SINGLE CONNECTION 110.14
2. GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS NOT SPLICED - 250.64
3. MAIN BREAKER TO HAVE MANUFACTURES HOLD DOWN AND PLASTIC OF PANEL FRAME BROKED
4. SERVICE STILL IN DETERIORATED CONDITION #4 & 5 LAST INSPECTION
5. UNIT LOCKED - MESSAGE TO CALL LEFT NO NUMBER
CALL PHONE FROM PREVIOUS INSPECTION AND LEFT MESSAGE
01/30/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*