Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/13/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 02/07/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MULTIPLE TERMINATIONS AT GROUND LUG PER SINGLE CONNECTION 110.14 2. GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS NOT SPLICED - 250.64 3. MAIN BREAKER TO HAVE MANUFACTURES HOLD DOWN AND PLASTIC OF PANEL FRAME BROKED 4. SERVICE STILL IN DETERIORATED CONDITION #4 & 5 LAST INSPECTION 5. UNIT LOCKED - MESSAGE TO CALL LEFT NO NUMBER CALL PHONE FROM PREVIOUS INSPECTION AND LEFT MESSAGE |
|
| 01/30/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |