Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/27/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SEPERATE GROUNDS AND NEUTRALS AT SUB PANELS 2) IDENTIFY UNINSULATED NEUTRAL 3) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH APPROVED DEVICE 4) LABEL PANELS AND BREAKERS 5) SUPPORT CONDUITS PER CODE 6) TIGHTEN LOOSE FITTINGS 7) SECURE SUB PANEL TO STRUCTURE 8) MAINTAIN WORK SPACE FOR BOTH PANELS 9) HIGHEST BREAKER 6' 7" |