Permit: T11EL03217

Parcel: 10612122B

Inspection Status: Denied

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/11/2012 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/27/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SEPERATE GROUNDS AND NEUTRALS AT SUB PANELS
2) IDENTIFY UNINSULATED NEUTRAL
3) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH APPROVED DEVICE
4) LABEL PANELS AND BREAKERS
5) SUPPORT CONDUITS PER CODE
6) TIGHTEN LOOSE FITTINGS
7) SECURE SUB PANEL TO STRUCTURE
8) MAINTAIN WORK SPACE FOR BOTH PANELS
9) HIGHEST BREAKER 6' 7"