Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/21/2012 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/16/2012 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
SUB PANEL:
1) NEED CONDUCTOR PROTECTION 352.46 AND 300.4
2) FILL UNUSED PORTION OF OPENING IN BACK WITH A NON COMBUSTIBLE PRODUCT
3) MAINTAIN WORKING CLEARANCES 110.26
4) STILL NO EQUIPMENT GROUND CONDUCTOR
5) OK CONDUIT DEPTH