Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/16/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SUB PANEL: 1) NEED CONDUCTOR PROTECTION 352.46 AND 300.4 2) FILL UNUSED PORTION OF OPENING IN BACK WITH A NON COMBUSTIBLE PRODUCT 3) MAINTAIN WORKING CLEARANCES 110.26 4) STILL NO EQUIPMENT GROUND CONDUCTOR 5) OK CONDUIT DEPTH |