Permit: T11EL03176

Parcel: 123022200


Addresses:

2556 E LINDEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/12/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/09/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SMOKE DETECTOR IN NORTH BEDROOM MUST BE AT LEAST 3' FROM THE A/C REGISTER
2) SMOKE DETECTORS ARE REQUIRED OUTSIDE OF BEDROOMS AS WELL AS INSIDE. ONE DETECTOR BETWEEN THE 2 BEDROOMS SHOULD SUFFICE
3) WATER HEATER PRESSURE RELIEF VALVE CANNOT HAVE A SIZE REDUCING FITTING. IT MUST HAVE A 3/4" PIPE RUN DOWN TO WITHIN 6" OF THE FLOOR
3)