Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING ELECTRODE CONDUCTOR MISSING-FRONT DISCONNECT NEEDS LABELING 2) BOND SECURE NIPPLES FOR NEW CONDUCTORS 250.92 3) VERIFY LUGS LISTING FOR (2) CONDUCTORS 4) EXTENSIVE M/C & CONDUIT ON EXTERIOR OF BLDGS, NOT TO CODE 5) BROKEN EXTERIOR RECEPT COVER 6) DAMAGED BOX AND CONDUIT CONNECTIONS-GATE MOTOR 7) LOCKED AND NO ACCESS TO BLDG |