Permit: T11EL03157

Parcel: 137293630


Addresses:

1760 W TENNYSON DR

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
02/27/2012 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
12/08/2011 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LOCATION OF NEW CONDENSOR DOES NOT ALLOW PROPER CLEARANCE IN FRONT OF PANEL PER CODE
2) SECURE LIQUID TIGHT AT CONDENSOR PER CODE
3) NEW SQUARED D 40 AMP CONDENSOR BREAKER MUST MATCH PANEL TYPE. NOT ABLE TO READ CONDENSOR I.D. TAG FOR CIRCUIT INFO
4) ADDED FLOOD LIGHT EXTERIOR CIRCUITS NOT INSTALLED TO CODE. OMIT OR INSTALL TO CODE
5) OMIT EXTERIOR OUTLET AT REAR PORCH. HAZARDOUS WIRING METHOD
6) ALL ADDITIONS SHOULD BE ON RECORD
7) NOTES 1-5 FOR POWER