Permit: T11EL03126

Parcel: 134081000

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T11EL03126

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
12/29/2011 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
12/09/2011 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) KEYS DO NOT OPEN FRONT DOOR
2) DISCONNECT FROM THE SIDE I CAN SEE IT OPEN AND CAN SEE WIRES AT SERVICE CANNOT HAVE 3 WIRES ON SPLIT BOLT OR 2 WIRES ON ONE LUG
3) ON NORTH SIDE WIRE TO LIGHT LOOSE AND OFF WALL, STORAGE ROOM WIRE TO BE REMOVED OR INSTALLED PER CODE
4) CALL BACK WHEN YOU HAVE KEYS TO GET IN
5) WIRES ON LIGHT BOXES TO BE WIRE NUTTED OFF THRU OUT HOUSE
6) BACK PORCH WIRES TO BE INSTALLED TO CODE OR REMOVED
7) SOUTH BEDROOM REMOVE FAN HOUSING AND LIGHT FIXTURE ON WALL
8) HAVE ELECTRICIAN FIND SUB PANEL
12/07/2011 ELECTRIC - RECONNECT Denied IVRS - Inspection :
There is no access to the site.| 920*
1) NO ACCESS CODE AND NO MESSAGE