Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2012 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/30/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) SEAL ENTRANCE ABOVE CURRENT CARRING PARTS 2) TIGHTEN CONDUCTOR TERMINATIONS 3) FINISH PREVIOUS ITEMS 1 & 4 4) RECALL AFTER POWER |
|
| 01/03/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT RISER BELOW ROOF LINE 2) TIGHTEN LOOSE FITTINGS 3) CORRECTLY IDENTIFY GROUNDED CONDUCTOR 200.6 4) LABEL PANEL DIRECTORY 408.4-NO GENERAL LABELING 5) GAS AND WATER BONDS NOT CONNECTED 6) PROVIDE PHYSICAL PROTECTION FOR CABLES 334.15 (B) 7) PLEASE VERIFY PERMITS FOR OTHER WORK |