Inspection History Details
Permit: T11EL03079
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/06/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRIC ROOMS CONVERTED TO CLOSETS-PANELS NOT ALLOWED IN CLOSET-COMBUSTIBLES AND WORKING SPACE 2) INSTALL ALL BREAKERS AND CLEAN BOTTOM OF PANEL 3) ELECTRC SERVICE NOT ACCESSIBLE-MAINTAIN SPACE PER 110.26 |