Permit: T11EL03040

Parcel: 127021020


Addresses:

5252 E HAWTHORNE PL

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
12/22/2011 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
11/28/2011 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OPPERABLE SMOKE DETECTORS NEEDED IN HALLWAY AND ALL BEDROOMS
2) OUTLET COVER NEEDED NORTH EAST BEDROOM
3) HOT CONDUCTOR DISCONNECTED IN PANEL
4) HOT CONDUCTOR CONNECTED TO GROUND/NEUTRAL BAR AT PANEL
5) UNDERSIZED FEEDERS TO SUB PANEL FOR ACCESSORY BLDG
6) SEPERATE GROUNDS AND NEUTRALS AT SUB-PANEL
7) COVER PLATES MISSING IN ACCESSORY BLDG
8) WATER PROOF COVERS NEEDED AT EXTERIOR OUTLETS