Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) ON FINAL TO SEE BRANCH CIRCUITS LANDED |
|
| 11/29/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A 2ND GROUND ROD AT LEAST 6' FROM 1ST GROUND ROD 2) GROUND RODS MUST BE INSTALLED PER 250.53 2005 NEC 3) DRIVE GROUND RODS IN STRAIGHT OR FOLLOW GUIDE LINES IN ARTICLE 250.53 |