Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/23/2011 | ELECTRIC - FINAL | Denied | 1. SECURE PANEL TO CODE 2. 50 AMP A/C CIRCUIT WHITE NOT LEAD MUST BE RED OR BLACK (TAPE OK) 3. MISSING DISCONNECT OVER 6'-8" PANEL APPEARS TO BE ORIGINAL 4. REPLACE SHARP POINT SCREW DEAD FRONT 5. GROUNDED OUTLETS ON NON-GROUNDED CIRCUIT 6. SMOKE ALARMS BEDROOMS & HALLWAYS 7. ALL ADDITIONS SHOULD BE ON RECORD NOTES 1-6 REQUIRED FOR POWER |