Permit: T11EL03012

Parcel: 123090650


Addresses:

2514 E DRACHMAN ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
05/15/2012 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection :*
04/26/2012 ELECTRIC - SERVICE RELOCATION Partial Approval IVRS - Inspection :*
1) RECALL AFTER CROSS OVER
2) OK TO COVER PVC
04/20/2012 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO SERVICE CONDUCTORS
2) NO GROUNDING ELECTRODE SYSTEM
3) NO GAS OR WATER BONDS
4) ALL PVC CONDUITS TO BE MINIMUM 18" (300.5)
5) NO ADDRESS LABEL AT SERVICE
6) WILL NEED LISTED MAST BRACE KIT
7) DUE TO STAFFING AND WORK LOADS WE CANNOT SCHEDULE INSPECTIONS