Permit: T11EL02938

Parcel: 118036160


Addresses:

2601 W SAN JUAN TE

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
11/21/2011 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
11/16/2011 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ROMEX WIRING IN GARAGE FOR SECURITY LTG. NOT TO CODE (INSIDE AND OUTSIDE)
2) KITCHEN RECEPTS MISSING
3) PLUG UNUSED BREAKER SPACES IN SERVICE PANEL