Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11EL02905
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/28/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK NEW WALL |
|
12/05/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DO NOT CLOSE WALLS WITHOUT INSPECTIONS |
|
12/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEED TO ADD CIRCUIT REPAIR WORK TO PERMIT 2) NEED TO ADD RECONNECT TO PERMIT-POWER HAS BEEN OFF 13 MONTHS (10/30/2010) PER TEP 3) FINISH A/C WORK 4) SERVICE CORRECTIONS MADE OK TO MAIN LUGS PANELS |
|
12/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CALLED-NO ANSWER-CALLED OFFICE-WILL RESCHEDULE |
|
11/30/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) INSTALL BOND SCREW IN SERVICE DISCONNECTS 250.24 2) NO REDUNDANT GROUNDING PER 250.6 |