Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/02/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OMIT REAR FLOOD LIGHT FIXTURE NOT INSTALLED TO CODE 2) SERVICE PANEL ALTERED, NEW BOX INSTALLED 3) UNDERSIZED WIRING 14 AWG FEEDERS TO 30 AMP PANEL 4) LABEL CIRCUITS 5) PROVIDED WEATHERED CONNECTION PANEL TO A/C CONDUIT 6) OMIT ZIP CORD BEDOOM CEILING FAN 7) RELOCATE ANY SMOKE ALARM 36" FROM FORCED AIR REGISTERS 8) PROVIDE BUSHING AT HOME RUN ENTRACNCE 9) ALL ADDITIONS SHOUT BE ON RECORD 10) NOTES 1-8 FOR POWER |