Permit: T11EL02840

Parcel: 134261150

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/15/2011 ELECTRIC - SERVICE UPGRADE Approved
11/28/2011 ELECTRIC - SERVICE UPGRADE Partial Approval
11/22/2011 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BRANCH WIRES ON CKTS #1,3 & 5 TO SHORT, SHOULD NOT BE CROSSING BUSS AREA
2) EXPOSED PVC TO BE SCHEDULE 80 PER CITY ORDINANCE
3) NEUTRAL RISER CONDUCTOR TO BE WHITE NOT GREEN
4) NEED TO VERIFY GAS BONDING
11/18/2011 ELECTRIC - SERVICE UPGRADE Denied SCHEDULE 40 PVC FOR UNDERGROUND ONLY, EXPOSED WORK SCHEDULE 80 PVC 300.50-B

LADDER TO INSPECT ROOF PVC MISSING STRAPS 352.30A