Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2011 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 11/28/2011 | ELECTRIC - SERVICE UPGRADE | Partial Approval | ||
| 11/22/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BRANCH WIRES ON CKTS #1,3 & 5 TO SHORT, SHOULD NOT BE CROSSING BUSS AREA 2) EXPOSED PVC TO BE SCHEDULE 80 PER CITY ORDINANCE 3) NEUTRAL RISER CONDUCTOR TO BE WHITE NOT GREEN 4) NEED TO VERIFY GAS BONDING |
|
| 11/18/2011 | ELECTRIC - SERVICE UPGRADE | Denied | SCHEDULE 40 PVC FOR UNDERGROUND ONLY, EXPOSED WORK SCHEDULE 80 PVC 300.50-B LADDER TO INSPECT ROOF PVC MISSING STRAPS 352.30A |