Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2011 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/02/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MUST USE A LISTED RISER SUPPORT-HOMEMADE OUT OF EMT NOT APPROVED 2) GROUND RODS MUST BE 6' MINIMUM APART 3) USE APPROVED CLAMP FOR #4 BARE GOING THRU -1/2" KO AT BOTTOM OF PANEL TO SECURE TO ENCLOSURE 4) BOND WATER/GAS PIPING |