Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/22/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL ENTRANCE ABOVE CURRENT CARRING PARTS WITH AN APPROVED DEVICE 2) SHEET METAL THREAD SCREWS NOT ALLOWD FOR GOUNDING 250.8 3) CLEAN SURFACE UNDER LUG 250.12 |
|
| 11/15/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXISTING DISC. SE (30 AMP) NOT RATED FOR OUTDOOR USE, REPLACE WITH NEMA 3 2) USE APPROVED FITTING WITH LOCK NUT FOR LB TERMINATION INTO PANEL |
|
| 11/01/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NO LOADS CONNECTED YET 2) CALL FOR FINAL AFTER TIE IN |