Permit: T11EL02795

Parcel: 125021070


Addresses:

2804 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/29/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/22/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL ENTRANCE ABOVE CURRENT CARRING PARTS WITH AN APPROVED DEVICE
2) SHEET METAL THREAD SCREWS NOT ALLOWD FOR GOUNDING 250.8
3) CLEAN SURFACE UNDER LUG 250.12
11/15/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXISTING DISC. SE (30 AMP) NOT RATED FOR OUTDOOR USE, REPLACE WITH NEMA 3
2) USE APPROVED FITTING WITH LOCK NUT FOR LB TERMINATION INTO PANEL
11/01/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NO LOADS CONNECTED YET
2) CALL FOR FINAL AFTER TIE IN